36 points croes 1 day ago 10 comments
geerlingguy 1 hour ago | parent
It also made me think about how many GitHub Actions I have that kick off on Sunday morning at a specific time. I try to vary the time/day for those jobs but I'm guessing there are enough things that kick off at specific time intervals to make an impact at the top of an hour, or at :15, :30, :45...
rmunn 1 hour ago | parent
If enough people used that, with a high enough value of N (say 1800 for jobs that really don't have to start at any particular time), it would greatly spread out the spikes in accidentally-coordinated usage.
schiffern 1 hour ago | parent
In this instance, one fix is to fire the timer every 59 seconds, so it will naturally drift out of phase with the minute hand of the clock. Or, if work needs to be done exactly every 60 seconds, then WAIT(RAND(60)) seconds for the timer initialization, so if 10,000 units start simultaneously they don't try all at once.
This is why many systems will do automated updates every 17 hours: 17 is coprime with 24.
Classic "thundering herd" mitigation tactics.
Edit: Tempting to blame IoT, but (since this is news) I don't think anyone knew there was something to fix here. We have the tools however.
HPsquared 36 minutes ago | parent
vlovich123 29 minutes ago | parent
But yeah, as soon as you start using Rand most people make all sorts of mistakes. And if you’re using C Rand, don’t. It has other statistical problems.
jagged-chisel 24 minutes ago | parent
vlovich123 14 minutes ago | parent
The other thing to watch out for is you’ve still got 1/60 of the thundering herd at the second level. If the tasks are <1s and you have enough of them (as you probably do at grid scale), then doing it finer grained is warranted like offsetting the timer by a millisecond sleep of 10 * uniform_distribution<int> between 0 and 6000. That then gives you 10ms granularity, distributing the workload by two more orders of magnitude.
mkj 24 minutes ago | parent
bob1029 1 hour ago | parent
The FFT indicates this is a periodic signal, not a once a day or week thing. It's happening continuously all day every day. I don't know of any UPS systems that perform tests with this kind of regularity.
In any case, I refuse to believe an external sync signal is causing this. The more likely explanation is that the active elements are pulling each other to a common mode due to being physically coupled on the same grid. This is like how clocks on the same beam will synchronize.
the8472 52 minutes ago | parent
From the article:
> The origin of these current peaks was independently confirmed by the manufacturer to be periodic self-tests executed by the battery EMS, confirming our interpretation. Similar minute-scale diagnostic routines are also documented for other commercial UPS systems (cf. Supplementary Note 8).
https://www.snaptec.com.au/akkutec-4801-din-user-manual.pdf
> battery circuit testing 1 x per minute for 1 sec
https://adelsystem.com/hubfs/PDF%20DC-UPS/Instruction%20Manu...
> The battery testing is carried out automatically every 60 sec.